Siemens 6SE7022-6TC61-Z Simovert VC Frequency Inverter

New 
On request
Refurbished   
1 available within 4 - 6 business days
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: SIMOVERT MASTERDRIVES | Series: Vector Control

The Siemens 6SE7022-6TC61-Z (Z=G11) is a Simovert VC frequency inverter from the SIMOVERT MASTERDRIVES Vector Control series. It provides vector-controlled operation of three-phase AC motors from a direct 510-650 V DC link supply, with a rated output current of 25.5 A and a rated power of 11 kW. The inverter connects to the DC bus and motor through power terminals and is intended for installed industrial drive systems, machine retrofits and replacement of matching SIMOVERT MASTERDRIVES VC units.

A replacement must match the 6SE7022-6TC61-Z part number, the G11 hardware option, the 510-650 V DC link supply and the installed communication configuration. PROFIBUS-DP is available through an optional CBP2 Communication Board, while CANopen is available through an optional CBC Communication Board. Parameters are stored non-volatilely in the Control Unit EEPROM and can be transferred with an OP1S Operator Panel or DriveMonitor/SIMOVIS, so commissioning may require parameter backup, transfer and configuration checks rather than a simple plug-in exchange.

The built-in PMU Parameterization Unit uses a seven-segment display for parameterization and status information. An OP1S User Panel provides parameterization, monitoring and parameter transfer, while DriveMonitor/SIMOVIS PC software version V3.32 provides an additional service interface. Alarm codes use the Axxx format and fault codes use the Fxxx format on the PMU or OP1S, with diagnostic parameters accessed through the control unit. As this Siemens drive is discontinued, a correctly matched used, refurbished or surplus replacement can support continued operation of installed SIMOVERT MASTERDRIVES equipment; ABC Industrial Parts can assist with preparing a replacement and transferring available parameters.

Technical Specifications

ManufacturerSiemens
Part number6SE7022-6TC61-Z (Z=G11)
Model/typeSimovert VC
Component typeFrequency inverter
Product familySIMOVERT MASTERDRIVES
SeriesVector Control
Rated power11 kW
DC link supply voltage510-650 V DC
Rated output current25.5 A
Control methodVector Control
Motor outputThree-phase AC motor output
DC bus interfacePower terminals
Motor output interfacePower terminals
PROFIBUS-DPOptional via CBP2 Communication Board
CANopenOptional via CBC Communication Board
Parameter storageNon-volatile EEPROM on Control Unit
Parameter transferSupported via OP1S Operator Panel or DriveMonitor/SIMOVIS
Z-optionG11
Lifecycle statusDiscontinued

Programming and Configuration

Drive configuration and service are supported through the PMU Parameterization Unit, the OP1S User Panel and DriveMonitor/SIMOVIS PC software version V3.32. The PMU provides a built-in seven-segment display for parameterization, while OP1S supports parameterization, monitoring and parameter transfer.

Parameters are stored non-volatilely in the Control Unit EEPROM. An OP1S panel can transfer settings from a faulty drive to a replacement unit, and DriveMonitor/SIMOVIS can be used for parameter transfer and service work. Replacement commissioning should include a check that the transferred parameters, firmware and installed hardware options match the existing drive configuration.

Communication and System Integration

The DC bus and three-phase AC motor connect through power terminals. The 6SE7022-6TC61-Z supports optional fieldbus integration according to the installed hardware configuration rather than through a fixed standard communication fit.

PROFIBUS-DP is available with a CBP2 Communication Board, and CANopen is available with a CBC Communication Board. When replacing a drive in an existing SIMOVERT MASTERDRIVES system, the installed communication board and the associated network configuration should match the original unit.

Diagnostics and Status Indication

The PMU Parameterization Unit displays alarm and fault information on its built-in seven-segment display. Alarm identifiers use the Axxx format, while fault identifiers use the Fxxx format. The OP1S User Panel provides parameterization and monitoring functions for service work.

Diagnostic parameters are accessed through the control unit, with DriveMonitor/SIMOVIS PC software version V3.32 providing an additional service interface. For a replacement drive, check the PMU or OP1S indication, review the displayed alarm or fault identifier and compare the parameter configuration before returning the unit to operation.

Replacement and Spare Part Considerations

Replacement selection should confirm the complete Siemens part number 6SE7022-6TC61-Z, the G11 Z-option, the 11 kW rating, the 25.5 A rated output current and compatibility with the installed 510-650 V DC link system. The motor output is for a three-phase AC motor, and the replacement must also match the communication hardware fitted to the original drive.

Check whether the existing installation uses a CBP2 Communication Board for PROFIBUS-DP or a CBC Communication Board for CANopen. Parameter transfer can be performed with an OP1S Operator Panel or DriveMonitor/SIMOVIS, using the non-volatile parameters stored in the Control Unit EEPROM where they remain available.

The 6SE7022-6TC61-Z is a discontinued Siemens drive. A correctly matched used, refurbished or surplus unit can maintain an installed SIMOVERT MASTERDRIVES system, provided the hardware option, communication configuration and transferred parameters are aligned before commissioning.

Frequently Asked Questions

What is the Siemens 6SE7022-6TC61-Z used for?

It is a SIMOVERT MASTERDRIVES Vector Control frequency inverter for three-phase AC motor operation from a 510-650 V DC link supply. Its rated power is 11 kW and its rated output current is 25.5 A.

What must match when replacing a 6SE7022-6TC61-Z?

Check the complete part number, the G11 Z-option, the 510-650 V DC link supply, the 11 kW and 25.5 A ratings, the three-phase motor connection and the installed communication board configuration.

How can parameters be transferred to a replacement drive?

Parameters can be transferred with an OP1S Operator Panel or DriveMonitor/SIMOVIS. The Control Unit stores parameters non-volatilely in EEPROM.

Which communication options are available?

PROFIBUS-DP is available through an optional CBP2 Communication Board. CANopen is available through an optional CBC Communication Board. The installed board should match the existing system.

How are alarms and faults shown on the drive?

The PMU Parameterization Unit and OP1S User Panel display alarm identifiers in Axxx format and fault identifiers in Fxxx format. Diagnostic parameters are accessed through the control unit.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Siemens.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.